L-DALI User Manual
250
LOYTEC
Version 5.2
LOYTEC electronics GmbH
nvoXXEnergyCnt
Type
SNVT_elec_kwh
Valid Range
0..65534
Resolution: 1kWh
Default Value
-
Description
This network variable reports the energy consumption of a group or channel.
L-DALI calculates the energy consumption of each DALI ballast. To reduce the number of
network variables, the calculated value is not available as a network variable on the lamp actuator
object but is used to calculate the total energy consumption for the group and channel actuator
objects.
The network variable
nvoGPEnergyCnt
reports the total energy consumption of all lamps in a
group.
The network variable
nvoCHEnergyCnt
reports the total energy consumption of all lamps in a
channel.
The nominal power of a lamp can be configured using the configuration property
nciNominalPwr.
The energy consumption of a lamp can be initialized with the configuration property
nciEnCntInit
.
nvoXXFailure
Type
SNVT_switch
Valid Range
.value:
0..100%
.state:
0, 1, -1
Default Value
-
Description
This network variable reports the status of the lamps in a group or channel.
The network variable
nvoGPFailure
reports the percentage of failed ballasts in a group.
The network variable
nvoCHFailure
reports the percentage of failed ballasts in a channel.
A ballast failure is reported if either
Bus power for the related DALI channel fails,
The DALI ballast is not reachable via the DALI channel, or
The DALI ballast reports a failure (e.g. lamp failure) in its DALI status register.
nvoPowerOff
Type
SNVT_switch
Valid Range
.value:
0, 100
.state:
0, 1
Default Value
-
Description
This network variable is used during the emergency light test to cut the power.
The power is cut with an ON value (100.0, 1) and reapplied with an OFF value (0.0, 0).