L-DALI User Manual
288
LOYTEC
Version 5.2
LOYTEC electronics GmbH
nviIllumLev
Type
SNVT_lux
Valid Range
0..65,335 lux
Default Value
-
Description
This network variable input provides the illumination level in the room. The input is used for view
protection (see Section 8.2.9.2). If
nviIllumLev
is higher than the
nviSunLux
then the sunblind is
closed to protect the room against prying eyes.
nviScene
Type
SNVT_scene
Valid Range
0..65,335 lux
Default Value
.function:
SC_LEARN, SC_RECALL, SC_NUL
.scene_number: 1..16
Description
Using this input network variable up to 16 sunblind scenes can be saved and recalled.
Function
Description
SC_LEARN
Stores the current sunblind position and rotation in the specified
scene number.
SC_RECALL
Recall a previously stored scene.
SC_RESET
Delete a scene.
nviWindowContact
Type
SNVT_switch
Valid Range
.value:
0..100%
.state:
0, 1
Open:
.state=1 and .value=100
Closed:
.state=0 and .value=0
Default Value
-
Description
This network variable input informs the controller if the window is open or close.
If the window is open, the sunblind stops moving.
nviOverride
Type
SNVT_switch
Valid Range
.value:
0..100%
.state:
0, 1
On:
.state=1 and .value>=0.5%
Off:
.state=0 and .value=0
Default Value
-
Description
This network variable input is used to switch on/off override mode.
If override mode is activated (.state=1 and .value between 0.5% and 100%), the sunblind adopts
the setting specified by
nciOverrideValue
.