Configuration Properties
All configuration properties listed in this section are implemented as Configuration
Parameters using configuration files (CPT, CPV, and CPC files). File access is provided via
L
ON
M
ARK
FTP.
nciLocation
Type
SCPTLocation (SNVT_str_asc)
Valid Range
31 ASCII characters
Default Value
Sunblind Ctrl X
Description
This configuration property can be used to specify the name of the sunblind controller.
nciMaxSendTime
Type
SCPTmaxSendTime (SNVT_time_sec)
Valid Range
0..6553.4 sec
Resolution: 0.1 sec
Default Value
0 sec
Description
Maximum time between updates for the
nvoSblndSetting
and
nvoSblndState
outputs (heartbeat
functionality).
nciMaxRcvTime
Type
SCPTmaxRcvTime (SNVT_time_sec)
Valid Range
0..6553.4 sec
Resolution: 0.1 sec
Default Value
0.0 sec (disabled)
Description
This configuration property specifies the expected update interval of the
nviWindowContact
network variable input. If the time elapses without an update of the variable an alarm is generated
and the sunblind adopts the safe position defined by the
nciWinConFailPos
.
nciWinConFailPos
Type
SCPTdefaultSetting (SNVT_setting)
Valid Range
.function:
SET_NUL (-1):
Invalid Value
SET_DOWN (2) Decrease setting by specified value
SET_UP (3)
Increase setting by specified value
SET_STOP (4)
Stop action
SET_STATE (5) Setting on at specified value
.setting:
0..100, resolution 0.5
.rotation: -359.98 .. 360.00, resolution 0.02
Default Value
SET_STATE, 0%, 0 deg
Description
This configuration property defines the safety position of a sunblind when a failure of the window
contact (
nviWindowContact