L-DALI User Manual
271
LOYTEC
Version 5.2
LOYTEC electronics GmbH
3.
Disable override: Ensure no override is active via the NV
nviCLOverride
(see Section
8.2.8.13
Input Network Variables
nviLuxLevel
Type
SNVT_lux
Valid Range
0..65,335 lux
Default Value
-
Description
This network variable input provides the illumination level measured by the light sensor.
If the variable is not bound, the
nvoLuxLevel
output of the light sensor object with the same
instance number as the constant light controller is used.
nviCLSetting
Type
SNVT_setting
Valid Range
.function:
SET_OFF (0):
Override to off.
SET_ON (1)
Enable/Relinquish override.
SET_DOWN (2) Decrease setpoint by specified value.
SET_UP (3)
Increase setpoint by specified value.
SET_STATE (5) Override to specified value.
.setting:
0..100, resolution 0.5
.rotation: not used
Default Value
Description
This network variable input is used to enable (SET_ON) or disable (SET_OFF) the controller, to
adjust the set point of the constant light controller (SET_UP and SET_DOWN) or to manually
update the
nvoLampValue
and the
nvoLamp2Value
(SET_STATE).
Function
Description
SET_OFF
Deactivates the constant light controller and switches off the lamp
value outputs
nvoLampValue
and
nvoLamp2Value.
SET_ON
Activates the constant light controller. Relinquishes any override.
SET_UP,
SET_DOWN
The set point of the controller can be increased (SET_UP) or
decreased (SET_DOWN) temporarily. The
.setting
value is used to
define the relative size of the increment/decrement
.
The changes
made to the set point are not stored permanently into the memory.
The next SET_ON command restored the original set point value
(
nciLuxSetpoint
).
SET_STATE
Deactivates the constant light controller and sets
nvoLampValue
and
nvoLamp2Value
to the value specified in the
.setting
field (see
Section 8.2.8.4).
nciLamp2Offset
and
nciLamp2Limit
are not
considered.