![LOYTEC L-DALI User Manual Download Page 41](http://html1.mh-extra.com/html/loytec/l-dali/l-dali_user-manual_1943336041.webp)
L-DALI User Manual
41
LOYTEC
Version 5.2
LOYTEC electronics GmbH
Figure 31: DALI Installation Web Interface: Group Configuration.
4.
To test the group assignment, lights can be switched on and off by clicking on the bulb
below the group name. Similar entering a value in the override row will dim the
corresponding group. Entering – in the field will relinquish an active override.
3.5.4 Calibrate Light Sensor
The L-DALI device allows calibrating the light sensor under up to seven different light
conditions to counter any non-linearity of the sensor. However, in many cases it is enough
to calibrate the sensor with a single light condition which is near the setpoint. In this quick-
start only one lux measurement is performed.
1.
Go to the DALI Installation page and press the
Calibrate
button next to the sensor that
is to be calibrated. The DALI sensor calibration page is shown in Figure 32.
Figure 32: DALI Installation Web Interface: Sensor Calibration.
2.
Measure the current lux level at the reference area (e.g. desk) using a luxmeter.