L-DALI User Manual
246
LOYTEC
Version 5.2
LOYTEC electronics GmbH
nviXXSetting
Type
SNVT_setting
Valid Range
.function: SET_OFF, SET_ON, SET_UP, SET_DOWN, SET_STATE
.setting:
0..100%
Default Value
-
Description
Used to control the group/channel. This input is effective only if
nviXXOverride.state
is invalid (-1).
Function
Description
SET_UP,
SET_DOWN
The light is dimmed relatively by the amount defined in the .setting
field.
SET_STOP
Stop an ongoing fade.
SET_OFF
The light is switched off and the last light level is saved temporarily.
SET_ON
The light is switched on to the light level saved at the time of the last
SET_OFF command.
SET_STATE
Set the light to the level defined by the .setting field.
The light is dimmed in ramping mode (constant rate, configuration property
nciFadeRate
is used).
nviXXOverride
Type
SNVT_switch
Valid Range
.value:
0..100%
.state:
0, 1, -1
Default Value
-
Description
If
nviXXOverride
is valid (.state=0/1), the current lamp/group/channel output is saved temporarily and
the lamp/group/channel output is set to the specified value.
If
nviXXOverride
is set to invalid (.state=-1), the lamp/group/channel output is set to the previously
saved value.
The light is dimmed in fading mode (constant time, configuration property
nciFadeTime
is used).