L-DALI User Manual
221
LOYTEC
Version 5.2
LOYTEC electronics GmbH
5.
Data points can be removed from the trend by clicking
Remove
.
6.
If COV mode was selected, the COV increment is displayed in the
COV delta
column.
This value can be increased to produce less trend data. Note, that it cannot be lowered
under the trended data point’s own COV increment. Go to the data point configuration
to change the COV increment in this case.
7.
If the trended value of the data point shall be aggregated over the log interval, select the
desired aggregation in the
Type
column. Available options are
Min
,
Max
,
Avg
.
Tip!
For creating multiple curves with min, average, and maximum values, add the same data
point three times and select the different aggregation types.
8.
In addition, a special
Trend Enable
data point can be selected. If configured, the trend
log will only log data, if the value of this data point evaluates
true
, i.e., is not zero.
Click the
button to select a data point.
9.
To remove the enable data point, click the
Remove
button.
10.
When done with the data point setup, click
Save Changes
to leave the dialog.
Tip!
A shortcut to creating a trend log object and attaching a data point is to select a data point
in the data point manager, right-click on it and choose
Trend Datapoint
from the context
menu. This generates a trend log and links that data point to it.
7.13.3 Trend Triggers
Local trend objects in CEA-709 can be operated in
trigger mode
. In this mode, one or more
trigger data points cause the generation of a snapshot containing the values of the trended
data points at the time instant the trigger is activated. For a trend object, one or more trigger
conditions can be defined. Depending on the trigger data point type, the trigger conditions
can be refined.
Note, that the behavior of the trigger data point is influenced by the COV properties of the
data point. If the
Only notify on COV
property is checked, the data point triggers only if its
value changes to the value of the trigger condition. If that property is not checked, the data
point triggers on every write with a value that matches the trigger condition.
To Configure Trigger Data Points for Trending
1.
Select the trend object in the
Trend
sub-folder.
2.
Right-click and select
Configure Trend
from the context menu.
3.
Change to the
Triggers
tab.
Note:
Of course, you can also change directly to the
Triggers
tab when creating a trend object.
4.
Click the
Add…
button. A data point selection dialog opens.
5.
Select one or more data points and click
OK
.