L-DALI User Manual
290
LOYTEC
Version 5.2
LOYTEC electronics GmbH
nviOccupSensor
Type
SNVT_occupancy
Valid Range
OC_NUL (-1):
Invalid Value
OC_OCCUPIED (0):
Area is occupied
OC_UNOCCUPIED (1): Area is unoccupied
OC_BYPASS (2):
Ignored
OC_STANDBY (3):
Ignored
Default Value
-
Description
This network variable input provides the occupancy state measured by an occupancy sensor. A
hold time can be configured using the configuration property
nciHoldTime
.
nviOccManCmd
Type
SNVT_occupancy
Valid Range
OC_NUL (-1):
Invalid Value
OC_OCCUPIED (0):
Area is occupied
OC_UNOCCUPIED (1): Area is unoccupied
OC_BYPASS (2):
Area is temporarily occupied for the bypass period
OC_STANDBY (3):
Ignored
Default Value
-
Description
This network variable input can be used to manually control the occupancy state.
Value
Description
OC_NUL
This is the initial value after power-up and it remains until another
value is received. It is used to indicate that this network variable
input is invalid, unused or to cancel a previous command.
OC_OCCUPIED
The sunblind controller should operate in the occupied mode.
OC_UNOCCUPIED
The sunblind controller should operate in the unoccupied mode
OC_BYPASS
The sunblind controller should operate in the occupied mode for a
period of time defined by
nciBypassTime
.
nviGlare
Type
SNVT_switch
Valid Range
.value:
0..100%
.state:
0, 1,-1
On:
.state=1 and .value>=0.5%
Off:
.state=0 and .value=0
Auto
.state=-1
Default Value
-
Description
This network variable is used to override the automatic glare detection algorithm (see Section
8.2.9.1).
Value
Description
On
Glare condition.
Off
No glare condition.
Auto
Use automatic glare detection algorithm.