L-DALI User Manual
298
LOYTEC
Version 5.2
LOYTEC electronics GmbH
nciAutoEvMinTm
Type
UCPTautoDelay (SNVT_time_sec)
Valid Range
0..6553.4 sec
Resolution: 0.1 sec
Default Value
600 sec
Description
Use to specify the minimum time for the following events:
Weather sensor alarm
Window sensor alarm
Frost condition
Wind
Rain condition
Window open
Anti-glare
View protection
Constant light request
Up if occupied
Heating/cooling request
The event will stay active for at least the configured time even if the event condition disappears
before this time expires. In this way the sun blind controller ensures that the sunblind does not
drive too frequently.
nciCLNumber
Type
UCPTobjectIndex (SNVT_count)
Valid Range
0..15
0xFFFF invalid
Default Value
0xFFFF (no Constant Light Controller linked)
Description
This configuration property specifies the index of the constant light controller that is linked to the
sunblind controller (see Section 8.2.8.7 und 8.2.8.11).
Object indices start with index 0.
8.2.10 Globals #0005
The L-DALI provides one Globals object for each DALI channel. It provides global
network variable inputs and configuration properties which are not specific for a certain
constant light controller or sunblind controller.