L-DALI User Manual
333
LOYTEC
Version 5.2
LOYTEC electronics GmbH
Property Identifier
Property
ID
Property Datatype
Conformance
Code
Object_Identifier
75
BACnetObjectIdentifier
R
Object_Name
77
CharacterString
R
Object_Type
79
BACnetObjectType
R
Present_Value
85
REAL
R
Status_Flags
111
BACnetStatusFlags
R
Event_State
36
BACnetEventState
R
Reliability
103
BACnetReliability
R
Out_Of_Service
81
BOOLEAN
W
Units
117
BACnetEngineeringUnits
R
Min_Pres_Value
69
REAL
R
Max_Pres_Value
65
REAL
R
COV_Increment
22
REAL
W
Time_Delay
113
Unsigned
W
Notification_Class
17
Unsigned
W
High_Limit
45
REAL
W
Low_Limit
59
REAL
W
Deadband
25
REAL
W
Limit_Enable
52
BACnetLimitEnable
W
Event_Enable
35
BACnetEventTransitionBits
W
Acked_Transitions
0
BACnetEventTransitionBits
W
Notify_Type
72
BACnetNotifyType
W
Event_Time_Stamps
130
BACnetARRAY[3] of BACnetTimeStamp
R
Profile_Name
168
CharacterString
R
Device_Failure
529
BIT STRING
RV
Ballast_Failure
530
BIT STRING
RV
Lamp_Failure
531
BIT STRING
RV
Battery_Failure
532
BIT STRING
RV
Function_Test_Failure
533
BIT STRING
RV
Duration_Test_Failure
534
BIT STRING
RV
Table 35: Properties of the Analog Input object representing the health state of a DALI channel.
Object_Identifier (Read-Only)
The default instance number is ABCC, where “A” is 3 for the objects associated with DALI
groups, and 4 with DALI channels, “B” is the DALI interface number (0-3) in decimal, and
“CC” is the DALI group address (00-15) in decimal (00 for DALI channels). Examples:
Group 5 on channel 1 has the instance number 3005, and channel 4 has the instance number
4300.
Object_Name (Read-Only)
This property holds the value of the
Object_Name
of the associated Analog Output object
with the addition “
Status
”.
Object_Type (Read-Only)
The value of this property is ANALOG_INPUT (0).