Figure 192: Create New Alarm Server dialog box.
7.12.2 Create an Alarm Condition
To generate alarms from data points, intrinsic reporting is used. For each data point an
alarm condition must be defined. This condition employs an intrinsic algorithm to generate
alarms based on the data point’s value or by evaluating a feedback value. Depending on the
data point type (analog, binary, multi-state), different conditions are defined. The alarm is
reported to the attached alarm server.
To Create an Intrinsic Alarm Condition
1.
Select a data point.
2.
Right-click and select
Create Alarm Condition…
from the context menu.
3.
For the alarm condition edit the following definitions, which apply to all condition
types as shown in Figure 193. Select the
Alarm Server
which the alarm shall be
reported to. Typically, you will choose a generic alarm server.
4.
Enter an
Alarm Message
. This is shown when the alarm becomes active. You may add
variable placeholders to this message by selecting one from the drop-down box
add
var
on the right-hand side. Enter a
Clear Message
. This is shown when the alarm
clears.
5.
Check the option
Enable Fault Alarms
, if fault conditions (offline, unreliable) shall
generate fault alarms. If enabled, enter a
Fault Message
, which is displayed along with
the fault alarm when it occurs.