L-DALI User Manual
324
LOYTEC
Version 5.2
LOYTEC electronics GmbH
Only present if the object is associated with a DALI lamp.
Min_Level (Read/Write)
The value of this proprietary property (property ID 516) corresponds to “MIN LEVEL” in
the DALI device. It must be in the range 0 < Min_Level <= 100.
Only present if the object is associated with a DALI lamp.
Groups (Read/Write)
The value of this proprietary property (property ID 517) is a 16-bit wide BIT STRING. It
corresponds to the “GROUPS” of the DALI device. It defines the group membership of a
lamp. Each bit corresponds to the group of the same index. If the bit is set, the lamp is
member of the group.
Only present if the object is associated with a DALI lamp.
Nominal_Power (Read/Write)
This proprietary property (property ID 518) is used to specify the nominal power of a DALI
ballast. A value of 0 is used to specify AUTO. In this case the nominal power is read from
the ballast (if available).
Only present if the object is associated with a DALI lamp.
Burn_In_Time (Read/Write)
This proprietary property (property ID 519) is used to configure the burn in time for the
channel. The burn-in mode can be activated/deactivated via the Web-UI.
Only present if the object is associated with a DALI channel.
Dim_Mode (Read/Write)
The value of this proprietary property (property ID 520) is used to specify whether to use
ramping (1) or fading (0) when changing the current dim level by writing to the
Present_Value
property.
In case of ramping a constant dim rate is used. Thus, the duration of the dim process
depends on the difference between start and target value.
Fading is based on a constant dim duration. Thus, the duration of the dim process does not
depend on the difference between start and target value.
On_Delay_Time (Read/Write)
This proprietary property (property ID 521) is used to configure an on-delay time in
seconds.
Off_Delay_Time (Read/Write)
This proprietary property (property ID 522) is used to configure an off-delay time in
seconds.
Warn_Delay (Read/Write)
This proprietary property (property ID 523) is used to configure an off-warning time in
seconds. It defines the time during which the user will be notified that the light will be