Figure 60: BACnet Time Master Configuration.
5.2.15 BACnet Restart Notifications (LDALI-20X only)
The device can be configured to send out a BACnet restart notification every time the
device is starting. The list of recipients for this notification can be configured on the
BACnet Restart Notifications
tab. Click the
Add
button for adding a new line to the list.
Then choose the recipient type from the drop-down box; it can be etiher a device instance
number or a BACnet address. For broadcasting the restart notification, choose
Addr
and
type in an asterisk ‘*’ for a global broadcast or prefix it with a destination subnet, e.g. ’12:*’
as shown in Figure 61. Then click
Save Settings
to store the new recipient.
Figure 61: Broadcast BACnet restart notifications to a subnet.
5.2.16 BACnet ACL (Access Control List, LDALI-20X only)
The device provides a feature in BACnet/IP to filter packets from certain sources on the
BACnet/IP network. This feature is based on an access control list (ACL). An example of
the ACL configuration is shown in Figure 62.