L-DALI User Manual
297
LOYTEC
Version 5.2
LOYTEC electronics GmbH
nciHoldTime
Type
SCPTholdTime (SNVT_time_sec)
Valid Range
0..6553.4 sec
Resolution: 0.1 sec
Default Value
600 sec
Description
This configuration property defines the hold time for the occupied state. When the
OC_OCCUPIED value is received via
nviOccupSensor
the constant light controller remains in the
occupied state until the hold time has expired and then changes to the unoccupied state. If set to 0
the unoccupied state is entered when OC_UNOCCUPIED is received.
nciSblndEvtPrio
Type
UCPTsunblindEventPriority
Valid Range
.heat_cool_req:
-128..127
.up_if_occupied:
-128..127
.constant_light_req:
-128..127
.view_protect:
-128..127
.glare:
-128..127
.scene_sel:
-128..127
.global_req:
-128..127
.group_req:
-128..127
.local_req:
-128..127
.window:
-128..127
.override_req:
-128..127
.set_override_req:
-128..127
.rain:
-128..127
.wind:
-128..127
.frost:
-128..127
.window_sensor_alarm:
-128..127
.weather_sensor_alarm:
-128..127
.maintenance_req:
-128..127
.set_maintenance_req:
-128..127
Default Value
All 0
Description
This configuration property defines the priorities of sunblind events (see Section 8.2.9.9). Higher
values render higher priority.
If multiple events have the same priority then they are prioritized with the default priority.
Events can be disabled by setting a negative value for its priority.
Events
maintenance_req
and
set_maintenance_req
will always be the highest priority events.
Their value is used to define which of the two events has the higher priority.