L-DALI User Manual
278
LOYTEC
Version 5.2
LOYTEC electronics GmbH
nciDimCurve
Type
UCPTdimmingCurve
Valid Range
.used:
0, 1
.level_0: 0..100%, Resolution: 0.5
.level_1: 0..100%, Resolution: 0.5
.level_2: 0..100%, Resolution: 0.5
.level_3: 0..100%, Resolution: 0.5
.level_4: 0..100%, Resolution: 0.5
.level_5: 0..100%, Resolution: 0.5
.level_6: 0..100%, Resolution: 0.5
.level_7: 0..100%, Resolution: 0.5
.level_8: 0..100%, Resolution: 0.5
.level_9: 0..100%, Resolution: 0.5
.level_10: 0..100%, Resolution: 0.5
Default Value
.used = 0
.level_0 = 1%
.level_1 = 1.5%
.level_2 = 2.5%
.level_3 = 4%
.level_4 = 6.5%
.level_5 = 10%
.level_6 = 16%
.level_7 = 25%
.level_8 = 40%
.level_9 = 64%
.level_10 = 100%
Description
This configuration property permits to adjust the characteristic of the lamp for the human vision.
If DALI lights are used the default values can be kept.
nciHoldTime
Type
SCPTholdTime (SNVT_time_sec)
Valid Range
0..6553.4 sec
Resolution: 0.1 sec
Default Value
600.0 sec
Description
This configuration property defines the hold time for the occupied state. When the
OC_OCCUPIED value is received via
nviOccup
the constant light controller remains in the
occupied state until the hold time has expired and then changes to the unoccupied state. If set to 0
the unoccupied state is entered when OC_UNOCCUPIED is received.
Note: Setting the
nciHoldTime
to 0 does not work when using the Echelon LonMaker
Browser. As a workaround the LINX Configurator can be used to set the parameters. If used
in Plug-In mode parameter values will be synced to the LNS database when downloaded to
the L-DALI.