switched off shortly. During this time, the light is dimmed to 50% of the current level.
Lamps which cannot be dimmed (
Min_Level
=
Max_Pres_Value
) blink during this time.
Auto_Off_Time (Read/Write)
This proprietary property (property ID 524) is used to configure an auto-off time in
seconds. It determines the delay after which the lamp output is switched off automatically.
The timer is started after receiving a lamp ON command via the
Present_Value
property
The property
Auto_Off_Mode
modifies the behavior of the auto-off timer.
Auto_Off_Mode (Read/Write)
The value of this proprietary property (property ID 526) determines the behavior of the
auto-off timer. Possible values are:
DISABLE_ALL (0)
ENABLE_RESTART and ENABLE_BREAK not
set.
ENABLE_BREAK (1)
The auto-off-timer can be interrupted by writing to
the
Present_Value
.
ENABLE_RESTART (2)
The auto-off-timer is restarted whenever the
Present_Value
is written.
ENABLE_RESTART_BREAK (3)
ENABLE_RESTART and ENABLE_BREAK set.
Elapsed_Active_Time (Read/Write)
The value of this proprietary property (property ID 527) gives the accumulated time in
seconds, which the corresponding DALI lamp was switched on. For groups or channels it
gives the maximum time of all lamps in the group/channel. When writing 0 to this property
the value is reset. For groups and channels the value of all lamps in the group/channel are
reset.
Time_Of_Active_Time_Reset (Read-Only)
The value of this proprietary property (property ID 528) give the time and date the
Elapsed_Active_Time
property was last reset.
Intrinsic reporting
This object supports all properties required for intrinsic reporting. Per default only fault
alarms are enabled.
8.3.3.11
Analog Input Object
– Feedback from DALI ballast, group, or channel
This object is used to give feedback on the current dim level of DALI ballasts, DALI
groups, or DALI channels (see Table 31).