Address
Name / setting range / [default setting]
Info
0x6049:002
Velocity deceleration : Delta time
0 ... [10] ... 65535 s
Deceleration: time interval
0x605A
Quick stop option code
Device status after exiting the quick stop ramp.
•
Setting is only effective in the operating mode
= " CiA: Velocity
mode [2]".
2 Quick stop ramp > switch-on inhibited
Automatic change to the "Switch-on inhibited" device state.
•
The "Quick stop active [54]" status is reset to FALSE after ramp-down
to standstill.
6 Quick stop ramp > quick stop active
The inverter remains in the "Quick stop active" device state.
•
The "Quick stop active [54]" status remains TRUE until the "Quick
stop" function is activated.
0x605E
Fault reaction option code
Selection of the response to faults.
-2 DC braking
If possible, the motor is braked to standstill with the "quick stop" func-
tion. If this is not possible (e. g. in case of an encoder error), reverse cur-
rent braking or short-circuit braking are used for the braking process.
0 Coasting
The motor becomes torqueless (coasts down to standstill).
2 Quick stop
The motor is brought to a standstill with the "quick stop" function.
•
In the operating mode
= "MS: Velocity mode [-2]", the decel-
eration time set in is effective.
•
In the operating mode
= " CiA: Velocity mode [2]", the speed
change set in
is effective.
0x6060
Modes of operation
Selection of the operating mode.
0 No mode change/no mode assigned
No operating mode (standstill)
2 CiA: Velocity mode
CiA 402 velocity mode
Operating mode "CiA 402 Velocity mode (vl)"
8 Cyclic sync position mode
Operating mode "CiA 402 Cyclic sync position mode (csp)"
9 Cyclic sync velocity mode
Operating mode "CiA 402 Cyclic sync velocity mode (csv)"
10 Cyclic sync torque mode
Operating mode "CiA 402 Cyclic sync torque mode (cst)"
0x6061
Modes of operation display
•
Read only
Display of the current operating mode.
-11 Identification
-10 Test mode
0 No mode change/no mode assigned
No operating mode (standstill)
2 CiA: Velocity mode
CiA 402 velocity mode
8 Cyclic sync position mode
9 Cyclic sync velocity mode
10 Cyclic sync torque mode
0x6071
Target torque
-3276.8 ... [0.0] ... 3276.7 %
Setting of the setpoint torque for the torque operating modes.
•
100 % ≡ Motor rated torque
•
The inverter does not support the operating mode "CiA 402 torque
mode".
0x6074
Torque demand value
•
Read only: x.x %
Display of the setpoint torque.
•
100 % ≡ Motor rated torque
0x6079
DC link circuit voltage
•
Read only: x.xxx V
Display of the current DC-bus voltage.
0x6085
Quick stop deceleration
0 ... [2147483647] ... 2147483647
Change in velocity used for deceleration to a standstill if quick stop is
activated.
•
Setting is only effective in the operating mode
= " CiA: Velocity
mode [2]".
•
In operating mode
= "MS: Velocity mode [-2]", the decelera-
tion time set in is effective.
0x6502
Supported drive modes
•
Read only
Bit coded display of the operating modes supported.
Bit 1 CiA: Velocity mode
1 ≡ CiA 402 velocity mode is supported.
Bit 7 Cyclic sync position mode
1 ≡ Cyclic sync position mode is supported.
Bit 8 Cyclic sync velocity mode
1 ≡ Cyclic sync velocity mode is supported.
Bit 9 Cyclic sync torque mode
1 ≡ Cyclic sync torque mode is supported.
Configuring the network
EtherCAT
Basic setting and options
340