16.3.2.2
Suppress diagnostic messages to the IO controller
serves to set which error response in the inverter suppresses the alarm message
to the IO-Controller.
Parameter
Address
Name / setting range / [default setting]
Info
0x285A:001
Diagnostic settings: Alarm supression
0x0000 ... [0x0000] ... 0xFFFF
Bit coded selection of error responses in the inverter which suppress the
alarm message to the IO Controller.
•
Bit x = 1 ≡ suppress alarm message.
•
In the default setting "0", an alarm message is displayed for all error
responses.
Bit 0 Information
Bit 1 Warning
Bit 2 -
Bit 3 Trouble
Bit 4 -
Bit 5 -
Bit 6 -
Bit 7 Fault
Bit 8 Fault > CiA402
16.3.3
Process data transfer
The process data is used to control the inverter.
•
The process data is transmitted cyclically between the IO-Controller and the IO-Devices
participating in PROFINET.
•
The process data can be directly accessed by the IO controller. The data in the PLC, for
instance, are directly stored in the I/O area.
•
The process data length is 1 ... 16 double words (4 ... 64 bytes) for each direction.
•
The process data are transmitted 1 : 1 according to its sequence.
Configuring the network
PROFINET
Process data transfer