Address
Name / setting range / [default setting]
Info
0x6073
Max current
0.0 ... [150.0] ... 3276.7 %
Maximum overload current of the inverter.
•
100 % ≡ Motor rated current (
•
If the current consumption of the motor exceeds this current limit,
the inverter changes its dynamic behaviour in order to counteract this
exceedance.
•
If the modified dynamic behaviour fails to eliminate the excess cur-
rent consumption, the inverter outputs an error.
When (current actual value in %) exceeds
(max. current actual
value in %) the message 0x238A is displayed. This status is also displayed
in the following network status word bits:
•
0x400C:001 bit 14
•
0x400C:002 bit 2
0x6075
Motor rated current
0.001 ... [1.300] ... 500.000 A
•
Setting can only be changed if the inverter is inhibi-
ted.
The rated motor current that needs to be set here serves as a reference
value for different parameters that involve a setting for/display of a cur-
rent value in percent.
Example:
•
Motor rated current = 1.7 A
•
Max current
= 200 % Motor rated current = 3.4 A
0x6076
Motor rated torque
0.001 ... [0.600] ... 1000.000 Nm
•
Setting can only be changed if the inverter is inhibi-
ted.
The rated motor torque to be set here serves as a reference value for
different parameters with a setting/display of a torque value in percent.
Example:
•
Motor rated torque = 1.65 Nm
•
Max torque
= 250 % Motor rated torque = 4.125 Nm
0x6080
Max motor speed
0 ... [6075] ... 480000 rpm
Limitation of the maximum motor speed.
Basic setting
Motor data
Manual setting of the motor data
43