6.3
Defining control sources
This chapter describes the selection of the control source for various control signals.
Settings in the »EASY Starter«:
•
Tab Settings - Parameter dialog Technology application
6.3.1
Source of quick stop
A quick stop can be requested via the control word or via a digital input. Use the Source for
quick stop parameter to select which input is used.
Parameter
Address
Name / setting range / [default setting]
Info
0x5020:007
Application quick stop source
Selection of the signal source for activating the quick stop.
0 FALSE
1 TRUE
2 Digital input 1
3 Digital input 2
4 Digital input 3
5 Digital input 4
6.3.2
Source of error reset
An error can be reset via the fieldbus, the system bus or via a digital input. Use the Source for
error reset parameter to select which input is used.
0x5020:008
(Source reset error)
FALSE
TRUE
DigIn1
DigIn2
DigIn3
DigIn4
Application
Fig. 21: "Reset error" selection
Parameter
Address
Name / setting range / [default setting]
Info
0x5020:008
Source of fault reset
Selection of digital inputs for resetting errors.
0 FALSE
1 TRUE
2 Digital input 1
3 Digital input 2
4 Digital input 3
5 Digital input 4
Technology application (TA) basic settings
Defining control sources
Source of error reset
80