Address
Name / setting range / [default setting]
Info
0x6067
Position window
0 ... [1000] ... 4294967295 pos. unit
Setting of the symmetrical tolerance window around the target position
(
) for the target position detection.
If the actual position is within this tolerance window longer than the
time defined in
in [ms], the target position is deemed to be
reached and bit 10 ("target position reached") is set in the CiA402 status
word (
).
0x6068
Position window time
0 ... [0] ... 0 ms
Setting of time monitoring for the target position detection.
0 ≡ the position in the target window is evaluated without a time delay.
9.1.2
Interpolation
When you select an operating mode with cyclic setpoint selection, all setpoints are first led via
interpolators which divides down setpoint step-changes of the bus cycle to the cycle time of
the control loops.All interpolators together are parameterised via
( Interpolation
time period value ).
Parameter
Address
Name / setting range / [default setting]
Info
0x60C0
Interpolation sub mode select
Setting of the interpolation algorithm.
-1 Quadratic Interpolation
0 Linear Interpolation
0x60C2:001
Interpolation time period : Interpolation time period
value
0 ... [1] ... 255
Basic multiplier for the interpolation time interval.
0x60C2:002
Interpolation time period : Interpolation time index
-6 ... [-3] ... 0
Exponent for the interpolation time interval.
(0 60 2:002)
( 3)
0 60 2 : 001*10
1*10
0.001
1
x
C
t
x C
t
s
s
ms
-
=
=
=
=
Configure position control
Basic setting
Interpolation
157