Address
Name / setting range / [default setting]
Info
0x2636:007
Analog input 1: Dead band
0.0 ... [0.0] ... 100.0 %
Optional setting of a dead band that is placed symmetrically around the
frequency zero point.
•
If the analog input value is within the dead band, the output value for
the motor control is set to "0".
•
100 % ≡ maximum value of analog input (, , )
•
Example: Dead band 10% of 50Hz: -10V … 10V dead band -5Hz … 5 Hz,
0 … 10V dead band 0Hz … 5 Hz
0x2636:010
Analog input 1: Error response
Error response for analog input 1.
Associated error code:
•
28801 | 0x7081 - Analog input 1 fault
0 No response
1 Fault > CiA402
2 Warning
0x2636:013
Analog input 1: Minimum value for scaling
-200.0 ... [0.0] ... 200.0 %
Minimum value in percent for scaling the value at the analog input
(Value in percent ()).
0x2636:014
Analog input 1: Maximum value for scaling
-200.0 ... [100.0] ... 200.0 %
Maximum value in percent for scaling the value at the analog input
(Value in percent ()).
0x2DA4:005
Diagnostics of analog input 1: Scaled percent value
•
Read only: x.xx %
Current value of the analog input is resolved with 2 decimal places.
Display of the actual value at the analog input, scaled with the following
parameters:
•
Minimum value for scaling.
•
Maximum value for scaling.
0x263D:001
Analog inputs internal control: Activation
0 Aus
1 Ein
0x263D:002
Analog inputs internal control: AI1 internal control
-200.00 ... [100.00] ... 200.00 %
I/O extensions and control connections
Configure analog inputs
Analog input 1
310