7.8.4
Gearbox factor correction
Modified register properties lead to a changed, real register length. The difference to the par-
ameterised register length Sensor distance leads to corrections in always the same direction
(positive or negative).
This correction is inefficient and leads to increased energy consumption and increased
mechanical stress. The gearbox factor correction calculates the optimum setpoint velocity of
the master value in this case.
The correction value is determined from the mean value of the position errors. The correction
value affects the setpoint velocity of the master value axis. When the gearbox factor is adjus-
ted, the constant part of the position errors is eliminated and the correction is made in the
positive and negative directions.
If the selected gain is too high, this can lead to an excessive setpoint velocity.
Parameter name
Parameter index
Status
Function
Activation of gearbox factor correction
0x5041:016
TRUE
Activates gearbox factor correction
Gearbox factor correction gain
-
Affects the velocity at which the gearbox
factor correction adjusts the static error
Actual gearbox factor
-
Outputs the value of the gearbox factor
Max. gearbox factor correction
-
Specifies the maximum value of the gearbox
factor correction
When the corrected gearbox factor has been detected, corrective movements occur in the
positive and negative directions. The detected gearbox factor is permanently accepted with
bit 25 = TRUE of the Activation of gearbox factor correction parameter. 0x5041:016
If the parameter Activation of gearbox factor correction = FALSE, the value of the gearbox
factor can be modified. 0x5041:016
Parameter
Address
Name / setting range / [default setting]
Info
0x5041:016
Activate gearbox factor correction
Bit 0
FALSE
Gearbox factor correction deactivated
Bit 1
TRUE
Gearbox factor correction activated
Parameter
Address
Name / setting range / [default setting]
Info
0x5042:005
Actual gearbox factor
•
Read only
0x5041:011
Gearbox factor correction gain
0.0000 ... [0.1000] ... 214748.3647
0x5041:012
Max. gearbox factor correction
0.0000 ... [10.0000] ... 214748.3647
Configuring the "Sync and Correction" TA
Master value correction (register control)
Gearbox factor correction
142