Address
Name / setting range / [default setting]
Info
0x2388
PROFINET status
•
Read only
Bit coded display of the current Bus status.
Bit 0 Initialized
The network component is initialised.
Bit 1 Online
The network component has established a cyclic I/O communication
relationship to a communication partner.
Bit 2 Connected
After initialisation, the network component waits for a communication
partner and the system power-up.
Bit 3 IP address error
The IP address is invalid. Valid IP addresses are defined according to RFC
3330.
Bit 4 Hardware fault
Bit 6 Watchdog elapsed
PROFINET communication is continuously interrupted in the
"Data_Exchange" state, e.g. by cable break or failure of the IO Controller.
•
PROFINET communication changes to the "No_Data_Exchange" state.
When the watchdog monitoring time specified by the IO Controller has
elapsed, the response set in
is triggered in the inverter.
Bit 7 Protocol error
Bit 8 PROFINET stack ok
Bit 9 PROFINET stack not configured
Bit 10 Ethernet controller fault
Bit 11 UDP stack fault
0x2389:001
PROFINET error: Error 1
•
Read only
The parameter currently contains the error detected on the network.
•
The error values may occur in combination with the error values from
parameter
0 No error
1 Reserved
2 Unit ID unknown
3 Max. units exceeded
4 Invalid size
5 Unit type unknown
6 Runtime plug error
7 Invalid argument
8 Service pending
9 Stack not ready
10 Command unknown
11 Invalid address descriptor
0x2389:002
PROFINET error: Error 2
•
Read only
The parameter currently contains the error detected on the network.
•
The error values may occur in combination with the error values from
parameter
Bit 7 IP address error
The IP address is invalid. Valid IP addresses are defined according to RFC
3330.
Bit 8 Station name problem
The station name must be assigned according to the PROFINET specifica-
tion.
Bit 9 DataExch left
PROFINET communication is continuously interrupted in the
"Data_Exchange" state, e. g. by cable break.
•
PROFINET communication changes to the "No_Data_Exchange" state.
•
When the watchdog monitoring time specified by the IO Controller
has elapsed, the response set in is triggered in the inverter.
Bit 10 Stack boot error
Bit 11 Stack online error
Bit 12 Stack state error
Bit 13 Stack revision error
Bit 14 Initialization problem
The stack cannot be initiated with the user specifications. A reason
might be, e. g., a station name that does not correspond to the PROFI-
NET specification.
Bit 15 Stack init error
Configuring the network
PROFINET
Diagnostics
364