16.1.2
Basic setting
Set the following parameters.
Parameter
Address
Name / setting range / [default setting]
Info
0x605A
Quick stop option code
Device status after exiting the quick stop ramp.
•
Setting is only effective in the operating mode
= " CiA: Velocity
mode [2]".
2 Quick stop ramp > switch-on inhibited
Automatic change to the "Switch-on inhibited" device state.
•
The "Quick stop active [54]" status is reset to FALSE after ramp-down
to standstill.
6 Quick stop ramp > quick stop active
The inverter remains in the "Quick stop active" device state.
•
The "Quick stop active [54]" status remains TRUE until the "Quick
stop" function is activated.
0x605B
Shutdown option code
Defines the transition from the status "Operation enabled" to "Ready to
start".
0 Disable drive function
0: Immediate inverter disable (standard setting)
1 Slow down on quick stop ramp and disable
drive fun
1: "Quick stop" with subsequent inverter disable.
0x605E
Fault reaction option code
Selection of the response to faults.
-2 DC braking
If possible, the motor is braked to standstill with the "quick stop" func-
tion. If this is not possible (e. g. in case of an encoder error), reverse cur-
rent braking or short-circuit braking are used for the braking process.
0 Coasting
The motor becomes torqueless (coasts down to standstill).
2 Quick stop
The motor is brought to a standstill with the "quick stop" function.
•
In the operating mode
= "MS: Velocity mode [-2]", the decel-
eration time set in is effective.
•
In the operating mode
= " CiA: Velocity mode [2]", the speed
change set in
is effective.
0x607E
Polarity
0 ... [0] ... 0
•
Setting can only be changed if the inverter is inhibi-
ted.
Setting of the polarity of the position setpoint.
0 ≡ the position setpoint is interpreted as entered in
( Target
position ).
0x6085
Quick stop deceleration
0 ... [2147483647] ... 2147483647
Change in velocity used for deceleration to a standstill if quick stop is
activated.
•
Setting is only effective in the operating mode
= " CiA: Velocity
mode [2]".
•
In operating mode
= "MS: Velocity mode [-2]", the decelera-
tion time set in is effective.
16.1.3
Process input data
Information on the CiA 402 process input data can be found in the following sections:
•
Configure position control
Process input data (CiA 402 objects)
•
Configure speed control
Process input data (CiA 402 objects)
•
Configure torque control
Process input data (CiA 402 objects)
16.1.4
Process output data
Information on the CiA 402 process output data can be found in the following sections:
•
Configure position control
Process output data (CiA 402 objects)
•
Configure speed control
Process output data (CiA 402 objects)
•
Configure torque control
Process output data (CiA 402 objects)
Configuring the network
Device profile CiA 402
Process output data
317