20.2
3-phase mains connection 400 V
20.2.1
Rated data
Inverters
I95AE155F
I95AE175F
I95AE222F
I95AE240F
I95AE275F
I95AE311F
I95AE315F
Rated power
kW
0.55
0.75
2.2
4
7.5
11
15
Rated power
hp
0.75
1
3
5
10
15
20
Mains voltage range
3/PE AC 340 V ... 528 V, 45 Hz ... 65 Hz
Output voltage
3 AC 0-400 V
Rated mains current
without mains choke
A
2.5
3.3
7.8
12.5
20
28.4
-
with mains choke
A
2
2.6
5.3
9
15.7
22.3
28.8
Apparent output power
kVA
1.2
1.6
3.8
6.4
11
16
22
Rated output current
2 kHz
A
1.8
2.4
5.6
9.5
16.5
23.5
32
4 kHz
A
1.8
2.4
5.6
9.5
16.5
23.5
32
8 kHz
A
1.8
2.4
5.6
7.1
16.5
23.5
23.5
16 kHz
A
1.2
1.6
2.6
2.9
11
12
11
Power loss
2 kHz
W
38
44
76
116
186
256
342
4 kHz
W
39
46
80
122
197
272
363
8 kHz
W
45
54
99
154
252
351
471
16 kHz
W
45
54
99
154
252
351
471
at inverter disable
W
20
20
20
20
20
20
20
Cyclic mains switching
3 times per minute
Max. motor cable length shielded
Category C2 (2 kHz, 4 kHz, 8
kHz)
m
20
20
20
20
20
20
20
Category C3 (2 kHz, 4 kHz, 8
kHz)
m
35
35
35
35
35
35
35
without EMC category
m
50
50
50
50
100
100
100
Weight
kg
1.6
1.6
1.6
1.6
3.9
3.9
3.9
Weight
lb
3.5
3.5
3.5
3.5
8.6
8.6
8.6
Technical data