• Follow the suggested actions in the order in which they are listed in the Action column until the problem is
solved.
• See “
Parts listing - BladeCenter HX5
” on page 57 to determine which components are customer replaceable
units (CRU) and which components are field replaceable units (FRU).
• If an action step is preceded by “(Trained service technician only),” that step must be performed only by a
Trained service technician.
Error code
Description
Action
2018002
Option ROM resource
allocation failure.
Informational message that some devices might not be initialized.
1. Run the Setup utility (see “Using the Setup utility” on page 20).
Select
Start Options
from the menu and modify the boot sequence
so that you change the load order of the optional-device ROM code.
2. Run the Setup utility (see “Using the Setup utility” on page 20) and
disable unused resource to make more space available:
• Select
Start Options
• Select
Planar Ethernet (PXE/DHCP)
to disable the integrated
Ethernet controller ROM.
• Select
Advanced Functions
, followed by
PCI Bus Control
, and
then
PCI ROM Control Execution
to disable the ROM of the
adapters in the PCI slots.
• Select
Devices and I/O Ports
to disable any of the integrated
devices.
3. Replace the following components one at a time in the order shown,
restarting the server each time:
a. Expansion cards (see “Removing an I/O expansion card” on
page 119 and “Installing an I/O expansion card” on page 121).
b. (Trained service technician only) System board (see “Removing
the system-board assembly - BladeCenter HX5” on page 140
and “Installing the system-board assembly - BladeCenter HX5”
on page 142).
3
xx
0007 (
xx
can be 00-
19)
Firmware fault detected,
system halted.
1. Recover the server firmware to the latest level. Run the Setup utility,
select
Load Default Settings
, and save the settings to recover the
server firmware.
2. Undo any recent configuration changes, or clear CMOS memory to
restore the settings to the default values.
3. Remove any recently installed hardware.
3038003
Firmware corrupted.
1. Revert to a previous version of the firmware for the blade server.
2. If the blade server will not start, switch to the backup UEFI image.
Set switch 7 to the on position. See “System-board switches” on
page 13 for the location of switch 7.
3. Restart the server until you see F1 Setup or the Boot Device
selection.
4. Power down the server.
5. (Trained service technician only) Replace the system board (see
“Removing the system-board assembly - BladeCenter HX5” on page
140 and “Installing the system-board assembly - BladeCenter HX5”
on page 142).
3048005
Booted secondary (backup)
server firmware image.
Information only. The backup switch was used to boot the secondary
bank.
158
BladeCenter HX5 Blade ServerProblem Determination and Service Guide
Summary of Contents for BladeCenter HX5 1909
Page 6: ...iv BladeCenter HX5 Blade ServerProblem Determination and Service Guide ...
Page 16: ......
Page 34: ...18 BladeCenter HX5 Blade ServerProblem Determination and Service Guide ...
Page 72: ...56 BladeCenter HX5 Blade ServerProblem Determination and Service Guide ...
Page 292: ...276 BladeCenter HX5 Blade ServerProblem Determination and Service Guide ...
Page 296: ...280 BladeCenter HX5 Blade ServerProblem Determination and Service Guide ...
Page 303: ...Taiwan Class A compliance statement Appendix B Notices 287 ...
Page 304: ...288 BladeCenter HX5 Blade ServerProblem Determination and Service Guide ...
Page 310: ...294 BladeCenter HX5 Blade ServerProblem Determination and Service Guide ...
Page 311: ......
Page 312: ...Part Number 46W8208 Printed in China 1P P N 46W8208 ...
Page 313: ... 1P46W8208 ...