75
KATANA S610M Inverter Specialized for Elevator Manual
The forced
deceleration switch is one
of the necessary guarantees
for the safe operation of the
elevator. Generally
speaking, the higher the
rated speed of the elevator,
the more classes of forced
deceleration switches. The
relationship between the
rated speed of elevator and
the classes of forced
deceleration switch is
shown in the following
table:
Rated Speed
Classes of Forced
Deceleration Switch
≤1.75m/s
1
≤2.5m/s
2
≤4m/s
3
F20.16
Install quantity of leveling switch
0:1 piece
1:2 pieces
0
The S610M control system supports the use of one or two leveling switch. If only one level switch is used, it is necessary to
set its input point to the upper leveling.If two leveling switches are used, the input points of the two level switches are set to
the upper level and the lower level respectively.
F20.17
Time Adjustment of Curve S
0~90%
56%
This parameter is used to adjust the proportion of variable acceleration time during the whole acceleration and deceleration
process, so as to adjust the time of the two inflection points in the acceleration and deceleration process.
F20.17
small
big
T1/Tacc=T3/Tacc
small
big
T2/Tacc
big
small
F20.18
Mode of Leveling Switch
0~1
1