KATANA S610M Inverter Specialized for Elevator Manual
9: Operation enable of the inverter
If this function is effective, the inverter can operate normally.
If this function is ineffective, the inverter will halt during operation after delay F02.11, or be prohibited to start when standing
by.
If no terminal is set to have this function, the inverter is defaulted to have operation permission.
10: Emergency operation input
If effective, the inverter starts emergency operation.
11
:
Operating contactor feedback input (CSM)
12
:
Braking feedback input (BSM)
13
:
Up forced deceleration speed input (UPF)
14
:
Down forced deceleration speed input (DNF)
15: Upward leveling input
16: Downward leveling input
When set F00.02=4 (CAN communication distance control), If set quantity of leveling switches are 2 (F20.16=1), upward
leveing signal and downward leveling signal must be used simultaneously. If set quantity of leveling switches are 1 (F20.16=0), only
need use upward leveling signal, don’t need use downward leveling signal.
F07.10
Terminal filtering time
0
~
500ms
10
This function is to set the filtering time for input terminal detection. If the state of input terminal changes, the terminal state
change is regarded valid only when its state maintains the same after passing the set filtering time. Otherwise, the prior state keeps
valid. In this way, false operation caused by interference can be effectively reduced.
F07.11
Input terminal activeness setting
000
~
3FFH
000
This parameter defines positive and negative logic of input terminals.
Positive logic: when terminal Xi is connected with corresponding common port, the terminal is active; when they are
disconnected, the terminal is inactive.
Negative logic: when terminal Xi is connected with corresponding common port, the terminal is inactive; when they are
disconnected, the terminal is active.