KATANA S610M Inverter Specialized for Elevator Manual
Error
Code
Error
Description
Possible Causes
Solutions
E042
Error
of
hoistway
auto-tuning
switch
dislocation
0
The running range is
disconnected when doesn’t
encounter in down forced
exchange switch 1 during
downward running.
1
The running range is
disconnected when doesn’t
encounter in down end-station
leveling switch but encounter
in down forced exchange
switch 1 during downward
running.
2/1
1
The running range is
disconnected when encounters
in down end-station leveling
switch during downward
running.
4
Start running from down
end-station to upward, the
running range is disconnected
when doesn’t pass the first
leveling switch and down
forced excange 1 still doen’t
close.
40
Start running from down
end-station to upward, the
running range is disconnected
when has passed the first
leveling switch but down
forced excange 1 still doen’t
close.
41
Start running from down
end-station to upward, the
running range is disconnected
when down forced exchange
switch 1 has closed but switch
2 still doesn’t close ( more
than 1 pair of switches), or
down forced exchange switch
1 has closed but up forced
exchange switch 1 still doesn’t
close (only have 1 pair of
switches).