72
KATANA S610M Inverter Specialized for Elevator Manual
Total floors mean all floors from the bottom floor to the highest one, including floors of underground.
For example: a building with 10 ground floors and 2 unerground floors, so, F20.00=12
Before auto-tuning floor-height operation, must firstly to set correct quantity of floors.
F20.01
Current floor setting
0~F20.00
0
0: No action
1~F20.00: Change current floor to this value, via this parameter to correct floors when display wrong floor. Should be used
with caution!
F20.02
Operating speed
0.100~F00.04
1.500m/s
Operating speed means the largest speed reached by elevator during its automatical operation.
After revising operatiing speed and rated speed, must do hoistway auto-tuning again.
For example:
One elevator with rated speed 3m/s (F00.04), set F00.04=3.00. If set F20.02=2.50, the highest actual speed of this
elevator will be less than rated speed, the highest speed is 2.5m/s. After revise opeating speed F20.02, must do hoistway
auto-tuning again.
F20.03
Start frequency of car fast operation
0.00~5.00Hz
0
F20.04
Start terrace of car fast operation
0.00~Min (1.00, F20.02)
0
F20.05
Start terrace delay
0~10
(
unit: 5ms
)
2
Figure 6-12 Curve of Start terrace of car fast operation
When the static friction of the elevator is very large, the starting comfort of the elevator will get worse, and then the
step start mode can be selected. Before running the normal acceleration curve, walk a few steps so that the elevator can
overcome the starting static friction and then run the acceleration curve automatically.
F20.06
Delay time of low-speed starting
0.00~5.00s
0
This parameter is used to delay the setting time after the steps start and then send the normal curve frequency.
F20.07
Average acceleration and deceleration
0.10~2.00 m/s2
0.30