KATANA S610M Inverter Specialized for Elevator Manual
0: Forbidden
1: Enable
Group F10 VF Control Parameters
F10.00
V/F curve setting
0: user-defined V/F curve
1: 2.0 power curve
2: 1.7 power curve
3: 1.2 power curve
1
0
×
F10.01
V/F frequency 3
F10.03
~
F01.03
0.01Hz
0.00 Hz
×
F10.02
V/F voltage 3
F10.04
~
100.0
0.1%
0.0
×
F10.03
V/F voltage 2
F10.05
~
F10.01
0.01Hz
0.00 Hz
×
F10.04
V/F voltage 2
F10.06
~
F10.02
0.1%
0.0
×
F10.05
V/F frequency 1
0.00
~
F10.03
0.01Hz
0.00 Hz
×
F10.06
V/F voltage 1
0
~
F10.04
0.1%
0.0
×
F10.07
Torque boost cut-off
point
0.0
~
50.0 (relative to F01.03)
0.1%
10.0
○
F10.08
AVR function
0: no action
1: keeps acting
2: no action only when decelerating
1
2
×
F10.09
IF controls min. given
value
of
excitation
current
0~150%Io ( no-load current of
Motor)
1%
0
×
F10.10
IF controls step length
of excitation current
0~100
1
5
×
F10.11
VF slip compensation
gain
0~200%
1%
100%
×
F10.12
Filter time of VF slip
compensation
0~1000ms
1ms
200ms
×
F10.13
Reserved
Group F11 Performance Parameters
F11.00
Carrier frequency
Rated output current 48A or below
:
1.0~15.0KHz
0.1
8.0
×
Rated output current 60A~71A
:
1.0~10.0KHz
8.0
Rated
output
current90A
:
1.0~10.0KHz
7.0
Rated output current 110A~176A:
1.0~6.0KHz
4.0
F11.01
Voltage
regulation
selection
LED units digit:
BIT0: overmodulation enable
0: disenable
1: enable
BIT1: disposition method of
overmodulation zone
0: method 0
1: method 1
1
100
×