74
KATANA S610M Inverter Specialized for Elevator Manual
F20.12
Find leveling speed of none terminal
station
0.05~0.30 m/s
0.20
Figure 6-15 Curve of find leveling of none terminal station
When the elevator is returned to the automatic operating state from the maintenance, or after the fault is reset, if the
car is in the non-gate area, the elevator will level to the open area. In the process of automatic leveling, the running speed of
the elevator is F20.12 before the leveling signal is received during automatic leveling process; After receiving the leveling
signal, evenly reduce the speed to zero, the car stops at the level location and stop running.
F20.13
Hoistway auto-tuning speed
0.10~0.50 m/s
0.30
The elevator needs to conduct hoistway data auto-tuning before normal automatic operation. The controller can record
length of the leveling screen panel, the position of each forced switch and the leveling position of each floor, etc. With
20.13 setting value to do the hoistway auto-tuning. The data of the hoistway auto-tuning obtatined is calculated and
evaluated. If the data is accurate, the relevant data is saved. If the data is not reasonable, the error is reported and the reason
is given.
F20.14
Elevator Security Diagnosis
0: Prohinit
1: Start the security
diagnosis
0
If F20.07 and F20.17 are changed, the elevator safety diagnosis must be re-conducted. Set F20.14=1 to start safe
diagnosis. If the diagnosis is wrong, the system will report a failure and give the reason for the failure.
F20.15
Classes of Forced Deceleration Switch
1~3
1