35
KATANA S610M Inverter Specialized for Elevator Manual
Function Code
Parameter Name
Setting Range
Factory Default
Value
Tens digit: motor type selection
0: asynchronous
1: synchronous
F00.02
Operation mode selection
0
~
4
0
0. Under operation panel control: use RUN and STOP keys on the operation panel for run commands
control, and F00.03 for setting speed command.
1. Reserved
2. Under the terminal speed control: use the terminals UP (upward) and DN (downward) to control the
run commands and multi-speed terminals MS1~MS3 to set speed commands.
3. CAN communication speed reference/given control: operational command is given by CAN
communication. Speed command is given by multi-speed of CAN communication.
4. CAN communication distance control: operational command is given by CAN communication.
According to master PC communication set target floor, operating speed is directly berthed and
automatically calculated in the view of distance principle.
Attentions:
When speed instruction is given via analog, the positive and negative polarities of set speed
output are jointly determined by analog value and forward & reverse operation command. XNOR
logic exists here. For example, if AI1 is 0V
~
+10V, i.e. the polarity is forward and operation command
is reverse, the final result is reverse; if AI1 is 0V
~
-10V, i.e. the polarity is reverse and operation
command is reverse, the final result is forward. The polarities of the set speed is fully determined by
forward & reverse operation command (forward & reverse terminal operation or operating direction
set by keyboard control – F00.05) when the set speed is given via other speed instructions.
F00.03
Digital speed given by the operation
panel
0
~
F00.04
(
m/s
)
1.500
It defines the initial value of speed setting when the inverter is under operation panel control. This
function code can be modified to change running speed during operation and the modification can be saved
after re-powering on.
F00.04
Rated speed of the elevator
0.100
~
4.000m/s
1.500
F00.04 means the rated speed on the elevator nameplate, and all the speed set value through the
function codes should not exceed it.
F00.05
Running direction setting
0
~
1
0
0: In same direction; 1: In opposite direction