43
KATANA S610M Inverter Specialized for Elevator Manual
Function Code
Name
Setting Range
Factory Default Value
location couldn’t be identified correctly, also this parameter can be lessened when occure overcurrent error during
identifying.
6.3 Start & Stop Control Parameters (Group F02)
F02.08
Diagram 6-4 Elevator Start & Stop Timing Diagram
Function Code
Parameter Name
Setting Range
Factory Default Value
F02.00
Delay time of starting
0.00
~
2.00s
0.50
This parameter defines the delay time from the inverter receiving run commands to be in operation.
F02.01
Delay time of brake release when
starts
0.00
~
2.00s
0.50
This parameter defines the time from the inverter operating at zero-speed to outputting brake release command.
F02.02
Maintaining time of zero-speed
starting
0.00
~
4.00s
0.80
This parameter defines the time from brake release of the inverter to outputting speed. The maintaining time should be
set to 0.5s at least, in order to prevent slipping when the elevator starts.
F02.03
Starting speed
0.000~0.200m/s
0.00
This parameter defines the inverter’s initial speed at starting.
F02.04
Maintaining time of starting speed
0.00
~
2.00s
0.00
This parameter defines the maintaining time of inverter’s starting speed (F02.03).
F02.05
Delay time of braking when stops
0.00
~
2.00s
0.50
v
Contactor output
Converter operating
t
0
F02.03
F00.04
Target Speed
Operation command
Brake
Zero-speed
operating
F02.00
F02.01
F02.02
F02.05
F02.06
F02.07