106
KATANA S610M Inverter Specialized for Elevator Manual
Function Code
Name
Recommend set value
Remarks
wrong, the system will report a failure
and give the reason for the failure.
F20.15
Class
of
forced
deceleration switch
Set according to the
actual situation
F20.16
Instal quantity of
leveling switch
Set according to the
actual situation
F20.17
Time adjustment of
S curve
56%
F20.18
Leveling
switch
mode
Set according to the
actual situation
F20.19
Speed
of
slight
motion leveling
0.05m/s
F21.01
Start delay of
hoistway learn
bottom floor interval.
Set according to the
actual situation
Adjust according to the actual
situation
F22.00~F22.63
Leveling distance
compensation of
upward running
floor 1… floor 64
Set according to the
actual situation
Adjust according to the actual
situation
F23.00~F23.63
Leveling distance
compensation of
downward running
floor 1… floor 64
Set according to the
actual situation
Adjust according to the actual
situation
7.5 CAN Communication Speed Control
Elevator controller based on the current elevator control logic to calculate running direction and target speed of
motor, in the form of Can communication send to S610M, S610M receives multi-speed type target speed to
control the operation of the elevator according to set parameter of S curve.
For example, the rated speed of an elevator is 1.5m/s, and the operating mode of Can communication speed
control (F00.02=3) is adopted to constitute the elevator control system. S610M controls the brake and output
operation contactor. The maintenance operation is carried out by the elevator controller with multi-section speed
command, and the running speed is given by the combination of multi-section speed instruction.
7.5.1 Basic wiring diagram
(Take “Differential Frequency Dividing Output PG Card” as an
example)