GEK-113285A
G650 Generator Protection & Control System
F-3
APPENDIX F
F.1 FACTORY DEFAULT SETTINGS
F
PRODUCT SETUP>COMMUNICATION SETTINGS >DNP3 SLAVE (CONT.)
DNP3 SLAVE 1 > DNP3 SLAVE 2 > DNP3 SLAVE 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Scale for power
Power Scale Factor
1
N/A
[0.00001-0.0001-0.001-
0.01-0.1-1-10-100-1000]
Scale for energy
Energy Scale Factor
1
N/A
[0.00001-0.0001-0.001-
0.01-0.1-1-10-100-1000]
Other Scale factor
Other Scale Factor
1
N/A
[0.00001-0.0001-0.001-
0.01-0.1-1-10-100-1000]
Default deadband for Current Analog
Input points to trigger unsolicited
responses
Current Deadband
30000
N/A
[0 : 65535]
Default deadband for Voltage Analog
Input points to trigger unsolicited
responses
Voltage Deadband
30000
N/A
[0 : 65535]
Default deadband for Power Analog
Input points to trigger unsolicited
responses
Power Deadband
30000
N/A
[0 : 65535]
Default deadband for Energy Analog
Input points to trigger unsolicited
responses
Energy Deadband
30000
N/A
[0 : 65535]
Default deadband for Other Analog
Input points to trigger unsolicited
responses
Other Deadband
30000
N/A
[0 : 65535]
Size (in bytes) for message
fragmentation
Msg Fragment Size
240
1 byte
[30 : 2048]
Size customization and change of
DNP Binary Inputs point list
Binary Input Block 1
CTL EVENTS 1-16 N/A
[See DNP note2]
Size customization and change of
DNP Binary Inputs point list
Binary Input Block 2
CTL EVENTS 17-32 N/A
[See DNP note2]
Size customization and change of
DNP Binary Inputs point list
Binary Input Block 3
CTL EVENTS 33-48 N/A
[See DNP note2]
Size customization and change of
DNP Binary Inputs point list
Binary Input Block 4
CTL EVENTS 49-64 N/A
[See DNP note2]
Size customization and change of
DNP Binary Inputs point list
Binary Input Block 5
CTL EVENTS 65-80 N/A
[See DNP note2]
Size customization and change of
DNP Binary Inputs point list
Binary Input Block 6
CTL EVENTS 81-96 N/A
[See DNP note2]
Size customization and change of
DNP Binary Inputs point list
Binary Input Block 7
CTL EVENTS 97-
112
N/A
[See DNP note2]
Size customization and change of
DNP Binary Inputs point list
Binary Input Block 8
CTL EVENTS 113-
128
N/A
[See DNP note2]
Size customization and change of
DNP Binary Inputs point list
Binary Input Block 9
SWITCHGEAR 1-8 N/A
[See DNP note2]
Size customization and change of
DNP Binary Inputs point list
Binary Input Block 10
SWITCHGEAR 9-
16
N/A
[See DNP note2]
DNP NOTES
Note 1: Scale Factor
Note that a scale factor of 0.1 is equivalent to a multiplier of 10 (i.e. the value will be 10 times
Note 2: Binary Input Block Selection:
[NOT USED, CTL EVENTS 1-16, CTL EVENTS 17-32, CTL EVENTS 33-48,CTL EVENTS 49-
64, CTL EVENTS 65-80, CTL EVENTS 81-96, CTL EVENTS 97-112, CTL EVENTS 113-128,
SWITCHGEAR 1-8, SWITCHGEAR 9-16]
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...