2-20
G650 Generator Protection & Control System
GEK-113285A
2.4 TECHNICAL SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
2.4.2.7 INADVERTED GENERATOR ENERGIZATION (ACCIDENTAL ENERGIZATION) (50/27)
2.4.2.8 PHASE SHIFT-LOSS OF MAINS (78V)
2.4.2.9 LOSS OF EXCITATION (40)
Operating condition
Overcurrent
Arming condition
Undervoltage and/or Machine Offline
Overcurrent
Pickup level
0.00 to 160.00 A in steps of 0.01 A
Dropout level
97% to 98% of pickup level
Level Accuracy
Values at nominal frequency
±
0.5% of the reading
±
10 mA from 0.1 to 10 A
±
1.5% of the reading for higher values
Undervoltage
Pickup level
0.00 to 500.00 V in steps of 0.01 V
Dropout level
102% to 103% of pickup level
Level accuracy
±1% reading ±0.1% Full Scale from 10 to 500 V at nomi-
nal frequency
Operate time
<50 ms at 50 Hz, typically
Timing accuracy
±3.5% of operate time or 50 ms. (whichever is greater)
Snapshot Events
Selectable by setting
Loss of Mains Mode
One Phase
Phase Shift Angle
2.00 to 22.00 in steps of 0.01 degrees
Minimum Voltage
30 to 500 in steps of 1 V
Level accuracy
± 3º
Timing accuracy
±3.5% of operate time or 60 ms (whichever is greater)
Snapshot Events
Selectable by setting
Operating condition
Positive-sequence impedance
Characteristic
2 independent offset mho circles (Stages 1 and 2)
Center
0.10 to 300.00.
Ω
(sec.) in steps of 0.01
Radius
0.10 to 300.00.
Ω
(sec.) in steps of 0.01
Reach accuracy
±3%
Undervoltage supervision
Selectable by setting
UV superv. Level
0.0 to 500.0 v in steps of 0.1 V
Trip delay
0.00 to 65.54 s in steps of 0.01 s
Operate time
<50 ms at 50 Hz, typically
Timing accuracy
±3.5% of operate time or 50 ms. (whichever is greater)
Snapshot Events
Selectable by setting
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...