G650 Generator Protection & Control System
GEK-113285A
4.2 HUMAN MACHINE INTERFACE (HMI)
4 HUMAN INTERFACES. SETTINGS & ACTUAL VALUES
4
The format of the displayed screens is as follows:
Select the Fault report menu in text menu
If there is more than one fault record rotate the shuttle key and select the desired
record to be displayed.
First screen with general fault information:
Fault report #number, fault type, distance
and date and time.
Second screen with metering data for that fault record. All this data is a summary
from the fault report file that can be retrieved via EnerVista 650 Setup software.
Figure 4–20: FAULT REPORT NAVIGATION IN HMI
Possible fault types are as follows:
GROUND
Ground faults
AG phase A to ground
ABG phase AB to ground
BG phase BG to ground
BCG phase BCG to ground
CG phase CG to ground
CAG phase CAG to ground
PHASE
Phase to phase faults
AB phase A to phase B
BC phase B to phase C
CA phase C to phase A
3PHASE Three-phase
faults
(shown on the display as 3PH)
NAF
Fault type not calculated