GEK-113285A
G650 Generator Protection & Control System
F-11
APPENDIX F
F.1 FACTORY DEFAULT SETTINGS
F
SETPOINT > PROTECTION ELEMENTS > SENSITIVE GROUND CURRENT > SENSITIVE GROUND IOC (ENHANCED MODELS
ONLY)
SENSITIVE GROUND IOC 1> SENSITIVE GROUND IOC 2 > SENSITIVE GROUND IOC 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Input type
Input
PHASOR(DFT)
N/A
[PHASOR – RMS]
Pickup level
Pickup Level
0.100
0.001 A
[0.005 : 16.000]
Trip time
Trip Delay
0.00
0.01 s
[0.00 : 900.00]
Reset time
Reset Delay
0.00
0.01 s
[0.00 : 900.00]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > PROTECTION ELEMENTS > NEGATIVE SEQUENCE CURRENT > NEGATIVE SEQUENCE TOC >
NEGATIVE SEQUENCE TOC 1> NEGATIVE SEQUENCE TOC 2 > NEGATIVE SEQUENCE TOC 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Pickup level
Pickup Level
1.00
0.01 A
[0.05 : 160.00]
Curve shape
Curve
IEEE Ext Inv
N/A
[See list of curves]
Time Dial
TD Multiplier
1.00
0.01 s
[0.00 : 900.00]
Reset type
Reset
INSTANTANEOUS N/A
[INSTANTANEOUS –
LINEAR]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > PROTECTION ELEMENTS > NEGATIVE SEQUENCE CURRENT > NEGATIVE SEQUENCE IOC >
NEGATIVE SEQUENCE IOC 1> NEGATIVE SEQUENCE IOC 2 > NEGATIVE SEQUENCE IOC 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function name
Function
DISABLED
N/A
[DISABLED – ENABLED]
Pickup level
Pickup Level
30.00
0.01 A
0.05 – 160.00
Trip delay time
Trip Delay
0.00
0.01 s
0.00 – 900.00
Reset delay time
Reset Delay
0.00
0.01 s
0.00 – 900.00
Snapshot event generation
Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > PROTECTION ELEMENTS > NEGATIVE SEQUENCE CURRENT > GENERATOR UNBALANCE >
GENERATOR UNBALANCE 1> GENERATOR UNBALANCE 2 > GENERATOR UNBALANCE 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
Function Permision
Function
DISABLED
N/A
[DISABLED – ENABLED]
Generator Rated Full Load Current
Gen Unbal Inom
5.00
0.01 A
[0.00 : 10.00]
Pickup level for stage 1 (as a
percentage of Gen Unbal Inom)
Gen Unbal Stg1 Pkp
8.00
0.01 %
[0.00 : 100.00]
K (Negative sequence capability
constant) for stage 1
Gen Unbal Stg1 K
1.00
0.01
[0.00 : 100.00]
Minimum Operating time for stage 1
Gen Unbal Stg1 Tmin 0.3
0.1 s
[0.0 : 1000.0]
Maximum Operating time for stage 1
Gen Unbal Stg1 Tmax 600.0
0.1 s
[0.0 : 1000.0]
K for Linear reset of the stage
Gen Unbal Stg1 K-Rst 240.0
0.1
[0.0 : 1000.0]
Pickup level for stage 2 (as a
percentage of Gen Unbal Inom)
Gen Unbal Stg2 Pkp
3.00
0.01 %
[0.00 : 100.00]
Trip time for stage 2
Gen Unbal Stg2 Delay 5.0
0.1s
[0.0 : 1000.0]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...