5-94
G650 Generator Protection & Control System
GEK-113285A
5.5 CONTROL ELEMENTS
5 SETTINGS
5
5.5.8 ANALOG COMPARATORS
The G650 provides 20 different analog comparators in an analog comparator module located in the control elements part of
the device. Each analog comparator gives indication when the analog variable selected is inside or outside some minimum
and maximum threshold values.
The settings can be selected at
Setpoint > Control Elements > Analog Comparators
Table 5–89: ANALOG COMPARATORS SETTINGS
The analog comparator settings includes two global settings such as
Analog Function:
This setting allows enabling or disabling the analog comparators module. Each analog comparator can
not be enabled/disabled individually.
Analog Snapshot Events:
The snapshot event setting enables or disables the snapshot event generation for this element.
Besides the main settings there are some settings for each analog comparator (up to 20) as follows:
Analog Input:
Analog value selected by the user from the available analog variables in the device. This will be used to
make the comparison inside a set band for that magnitude.
Analog Maximum:
Maximum threshold value for the comparison band.
Analog Minimum:
Minimum threshold value for the comparison band.
Analog Delay:
Time value for the analog signal to be active inside the comparison band before setting the Analog Level
signal to 1.
Analog Hysteresis:
It establishes the deadband at each extreme. For the maximum value is the maximum minus the
hysteresis value (in %) and for the minimum value is the minimum value plus the hysteresis value (in %).
Analog Direction:
Analog direction for the activation signal to be set Inside or Outside the Deadband.
OUT:The "Analog Level X" will give an activation signal when the analog value is located outside the comparison
band.
IN:The "Analog Level X" will give an activation signal when the analog value is located inside the comparison band.
The G650 provides 20 different analog comparators. Their status values can be viewed at
Actual> Status > Control
Elements > Analog Comparators:
SETPOINT > CONTROL ELEMENTS > ANALOG COMPARATORS
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP RANGE
Generic Analog Function Permission
Analog Function
DISABLED
N/A
[DISABLED – ENABLED]
Generic Snapshot Events Generation
Analog Snapshot Events
DISABLED
N/A
[DISABLED – ENABLED]
Analog Input Value Selection
Analog Input X
None
N/A
[All available analog values]
Analog Maximum Threshold Value
Analog Maximum X
1.000
0.001 [-100000.000 : 100000.000]
Analog Minimum Threshold Value
Analog Minimum X
1.000
0.001 [-100000.000 : 100000.000]
Analog Delay for Activation Signal
Analog Delay X
0.00
0.01
s
[0.00 : 900.00]
Analog Hysteresis for the Deadband
Analog Hysteresis X
1.0
0.1
[0.0 : 50.0]
Analog Direction for Activation Inside or
Outside the Deadband
Analog Direction X
Out
N/A
[IN-OUT]
Note: X is the analog comparator index, up to 20
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...