C-16
G650 Generator Protection & Control System
GEK-113285A
C.5 DNP CONFIGURATION EXAMPLES
APPENDIX C
C
Figure C–2: SETTINGS FOR DNP3.0 MULTI-MASTER COMMUNICATIONS WITH G650
DNP 3.0 Slave – F650
Ethernet Config
IP Addr: 192.168.37.20
Netmask: 255.255.255.0
DNP 3.0 slave 1
Physical Port:
Network
Address: 255
IP Addr Cli1: 192.168.37.1
TCP/UDP Port :
20000
Unsol Dest Addr: 200
DNP 3.0 Master 1
Ethernet Config
IP Addr: 192.168.37.1
Netmask: 255.255.255.0
DNP3 over TCP/IP
DNP Addr:
200
DNP Dest Addr: 255
IP Dest: 192.168.37.20
TCP Dest Port: 20000
DNP 3.0 Master 2
Ethernet Config
IP Addr: 192.168.37.2
Netmask: 255.255.255.0
DNP3 over TCP/IP
DNP Addr:
201
DNP Dest Addr: 256
IP Dest : 192.168.37.20
TCP Dest Port: 20001
DNP 3.0 Master 3
Ethernet Config
IP Addr: 192.168.37.3
Netmask: 255.255.255.0
DNP3 over TCP/IP
DNP Addr:
202
DNP Dest Addr: 257
IP Dest: 192.168.37.20
TCP Dest Port: 20002
DNP 3.0 slave 2
Physical Port:
Network
Address: 256
IP Addr Cli1: 192.168.37.2
TCP/UDP Port :
20001
Unsol Dest Addr: 201
DNP 3.0 slave 3
Physical Port:
Network
Address: 257
IP Addr Cli1: 192.168.37.3
TCP/UDP Port :
20002
Unsol Dest Addr: 202
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...