5-86
G650 Generator Protection & Control System
GEK-113285A
5.5 CONTROL ELEMENTS
5 SETTINGS
5
Phase Angle Difference
Δϕ
In the live line-live bus Condition, once the voltage difference has been successfully verified in magnitude, the system
establishes the angle difference between both voltage phasors. If the angle difference is lower than the
Δϕ
set
(Max Angle
Difference) setting, then the system will verify the frequency slip
S
(Max Freq Difference).
Figure 5–17: VOLTAGE ANGLE DIFFERENCE
Frequency slip
Δ
f
The relative frequency slip between phasors is calculated if the angle difference is lower than the
Δϕ
set
(Max Freq
Difference) setting. From the information obtained from the relay, the algorithm will know the slip (mHz) of both phasors,
and it will take as reference (V
Ref
) the lowest frequency phasor.
If the relative slip is higher than 5 mHz, the element performs an anticipative algorithm, determining the right moment to
give the closing command to the breaker, so that the breaker closes when the line and busbar voltages are in phase. If the
slip is higher than 5 Hz, as an in phase close is not possible, the algorithm ensures that the difference between voltages in
the real closing moment is not higher than the set value (Max Volt Difference). If the relative slip,
Δ
f, is equal or lower than
0.005 Hz, the algorithm gives permission to close as soon as the angle difference conditions are met, because at such a
low speed, the hold time for getting an “in-phase” closing permission would be too long.
When the difference between voltage values equals “two times” the set angle as maximum angle difference (
Δ
V =
Δ
V
set
),
the anticipative algorithm starts running and uses the set breaker closing time to establish the initiation of permission, so
that it is executed in the moment when both voltage phasors are completely in phase, thus minimizing the voltage
difference in the breaker chamber to negligible values.
The main benefit is that after a considerable number of breaker operations, damage to internal connection elements, as
well as to the chamber isolating element is drastically reduced, ensuring a longer life for the breaker, and reducing costly
maintenance operations.
V
1
V
2
V
H
'M
actua
V
L
'M
set
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...