GEK-113285A
G650 Generator Protection & Control System
C-11
APPENDIX C
C.5 DNP CONFIGURATION EXAMPLES
C
C.5DNP CONFIGURATION EXAMPLES
C.5.1 CONFIGURING DNP USER MAP
Imagine that a user wants to configure DNP Binary Inputs Map with 8 Contact Inputs, 8 Protection states, 8 Contact
Outputs and 2 Switchgears. This configuration can be done in two steps. In first step the user selects
“Setpoint->Relay
Configuration”
from the EnerVista 650 Setup program and then configures
Control Events
bits and
Switchgear
bits. It is
shown in figures 9.1 and 9.2. In the second step the user selects
“Setpoint->System Setup->Communication settings-
>DNP”
in order to change DNP Binary Input Block settings. The user set values of the first three Binary Input blocks, Binary
Input Block1 = CTL EVENTS 1-16, Binary Input Block2 = CTL EVENTS 17-32, Binary Input Block3 = SWITCHGEAR 1-8. It
is shown in Configuration of Control Events bits13-1
Figure C–1: CONFIGURATION OF CONTROL EVENTS BITS
Figure C–2: CONFIGURATION OF SWITCHGEAR