GEK-113285A
G650 Generator Protection & Control System
3-7
3 HARDWARE
3.3 MECHANICAL DESCRIPTION
3
Figure 3–7: COMMUNICATIONS MEDIA SELECTOR GUIDE
Communication boards are installed at the rear part of the unit, the upper port being reserved for the asynchronous
communications board and CAN, and the lower port for the ETHERNET board in any of its configurations.
Figure 3–8: DETAIL OF INSERTION/EXTRACTION OF COMMUNICATION MODULES
The transformers module with the VTs and CTs is already connected to a female connector screwed to the case
that incorporates shorting bars in the current inputs, so that it can be extracted without the need to short-circuit
the currents externally. It is very important, for safety reasons not to change or swift the terminals for CTs and VTs.
TYPE OF COMMUNICATION
CONNECTOR
RS485 / CAN cable
Plug-in, 3 poles.
IRIG B
Plug-in, 2 poles.
Plastic fiber optic
Versatile Link
Ethernet 10/100 UTP (10/100BaseTX)
RJ45, Class 5.
Glass fiber optic (100BaseFX)
ST
Ethernet 100 FX (100BaseFX)
ST
CAN Fiber
ST