GEK-113285A
G650 Generator Protection & Control System
F-17
APPENDIX F
F.1 FACTORY DEFAULT SETTINGS
F
LOSS OF EXCITATION 1 > LOSS OF EXCITATION 2 > LOSS OF EXCITATION 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function Permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Center point in Ohms (sec) for Stage 1 Stage 1 Center
10.00
0.01 Ohm
[0.10 : 300.00]
Radius value in Ohms (sec) for Stage
1
Stage 1 Radius
8.00
0.01 Ohm
[0.10 : 300.00]
UV Supervision for stage 1
Stage 1 UV Supv
DISABLED
N/A
[DISABLED – ENABLED]
Trip time for Stage 1
Stage 1 Trip Delay
0.05
0.01 s
[0.00 : 65.54]
Center point in Ohms (sec) for Stage 2 Stage 2 Center
10.00
0.01 Ohm
[0.10 : 300.00]
Radius value in Ohms (sec) for Stage
2
Stage 2 Radius
8.00
0.01 Ohm
[0.10 : 300.00]
UV Supervision for stage 2
Stage 2 UV Supv
DISABLED
N/A
[DISABLED – ENABLED]
Trip time for Stage 2
Stage 2 Trip Delay
0.05
0.01 s
[0.00 : 65.54]
UV Supervision Level for both stages
1 and 2
UV Supv Level
40.0
0.1 V
[0.0 : 500.0]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...