GEK-113285A
G650 Generator Protection & Control System
B-131
APPENDIX B
B.7 MEMORY MAP
B
0x434E
UV Supv Level
F003
1
R/W
2
[0.0 , 500.0] V
0x4350
Snapshot Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x435A
Confirmation address
W
1
Ajustes Pérdida de Excitación Grupo 3 - Loss of Excitation 3 Settings
0x435B
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x435C
Stage 1 Center
F003
1
R/W
2
[0.10 , 300.00] Ohm
0x435E
Stage 1 Radius
F003
1
R/W
2
[0.10 , 300.00] Ohm
0x4360
Stage 1 UV Supv
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x4361
Stage 1 Trip Delay
F003
1
R/W
2
[0.00 , 65.54] s
0x4363
Stage 2 Center
F003
1
R/W
2
[0.10 , 300.00] Ohm
0x4365
Stage 2 Radius
F003
1
R/W
2
[0.10 , 300.00] Ohm
0x4367
Stage 2 UV Supv
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x4368
Stage 2 Trip Delay
F003
1
R/W
2
[0.00 , 65.54] s
0x436A
UV Supv Level
F003
1
R/W
2
[0.0 , 500.0] V
0x436C
Snapshot Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x4376
Confirmation address
W
1
Ajustes Sobrecorriente Instantánea de Secuencia Inversa Grupo 1 - Negative Sequence IOC 1 Settings
0x4377
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x4378
Pickup Level
F003
1
R/W
2
[0.05 , 160.00] A
0x437A
Trip Delay
F003
1
R/W
2
[0.00 , 900.00] s
0x437C
Reset Delay
F003
1
R/W
2
[0.00 , 900.00] s
0x437E
Snapshot Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x4388
Confirmation address
W
1
Ajustes Sobrecorriente Instantánea de Secuencia Inversa Grupo 2 - Negative Sequence IOC 2 Settings
0x4389
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x438A
Pickup Level
F003
1
R/W
2
[0.05 , 160.00] A
0x438C
Trip Delay
F003
1
R/W
2
[0.00 , 900.00] s
0x438E
Reset Delay
F003
1
R/W
2
[0.00 , 900.00] s
0x4390
Snapshot Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x439A
Confirmation address
W
1
Ajustes Sobrecorriente Instantánea de Secuencia Inversa Grupo 3 - Negative Sequence IOC 3 Settings
0x439B
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x439C
Pickup Level
F003
1
R/W
2
[0.05 , 160.00] A
0x439E
Trip Delay
F003
1
R/W
2
[0.00 , 900.00] s
0x43A0
Reset Delay
F003
1
R/W
2
[0.00 , 900.00] s
0x43A2
Snapshot Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x43AC
Confirmation address
W
1
ADDRESS BIT
NAME
FORMAT
STEP MODE LENGTH
MISCELLANEOUS
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...