GEK-113285A
G650 Generator Protection & Control System
F-19
APPENDIX F
F.1 FACTORY DEFAULT SETTINGS
F
SETPOINT > INPUTS/OUTPUTS > CONTACT I/O >
BOARD F > BOARD G >BOARD H>BOARD J
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
I/O board type (available only for CIO
modules)
I/O Board Type_
X
NONE
N/A
[NONE,
16 INP + 8OUT,
8 INP + 8OUT + SUPV
32 INP
16 INP + 8 ANA]
Input activation voltage threshold
Group A
Voltage Threshold
A_
X
80
1 V
[10 : 230]
Input activation voltage threshold
Group B
Voltage Threshold
B
_X
80
1 V
[10 : 230]
Input activation voltage threshold
Group C
Voltage Threshold
C_
X
80
1 V
[10 : 230]
Input activation voltage threshold
Group D
Voltage Threshold
D
_X
80
1 V
[10 : 230]
Debounce time for Group A
Debounce Time A
_X
15
1 ms
[1 : 50]
Debounce time for Group B
Debounce Time B
_X
15
1 ms
[1 : 50]
Debounce time for Group C
Debounce Time C
_X
15
1 ms
[1 : 50]
Debounce time for Group D
Debounce Time D
_X
15
1 ms
[1 : 50]
Input type
Input Type_
X
_CC
Y
(CC
Y
)
POSITIVE
N/A
[POSITIVE-EDGE,
NEGATIVE-EDGE,
POSITIVE,
NEGATIVE]
Input signal time delay
Delay Input
Time_
X
_CC
Y
(CC
Y
)
0
1 ms
[0 : 60000]
Output logic type
Output Logic_
X
_0
Z
POSITIVE
N/A
[POSITIVE,
NEGATIVE]
Output type
Output Type_
X
_0
Z
NORMAL
N/A
[NORMAL,
PULSE,
LATCH]
Output pulse length
Pulse Output
Time_
X
_0
Z
10000
1 ms
[0 : 60000]
Analog Inputs Range
Range_
X
_0
Z
NONE
N/A
[NONE,
-1 to 0mA,
0 to 1 mA,
-1 to 1 mA,
0 to 5 mA,
0 to 10 mA]
Minimum Value
Min_Value_
X
_0
Z
0.00
0.01
[ -9999.99 : 9999.99]
Maximum Value
Max_Value_
X
_0
Z
0.00
0.01
[ -9999.99 : 9999.99]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...