10-4
G650 Generator Protection & Control System
GEK-113285A
10.1 EXAMPLE 1: COMMUNICATION & PROTECTION SETTINGS PROCEDURE
10 APPLICATION EXAMPLES
10
Under
SETPOINT
⇓
RELAY CONFIGURATION
⇒
LEDS
Under
SETPOINT
⇓
RELAY CONFIGURATION
⇒
OPERATIONS
Select
Operation 0
Command Text
Reset C Output 00
Interlock Type
None
Interlocks
---
Final State Type
None
Final States
---
Frontal Key
F1
Contact Input
None
Virtual Output
None
Time Out
500 (default)
MMI
---
Com1
---
Com 2
---
ETH-Master 1
---
ETH Master 2
---
ETH Master 3
---
ETH Master 4
---
Under
SETPOINT
⇓
RELAY CONFIGURATION
⇒
OSCILLOGRAPHY
10.1.4 TEST
Apply 7.5 A in phase A (terminals B1-B2) until contact 00 on Board F operates (terminals F19-F21 should be and remain
closed), and LED 5 should be lit. Check that operating time is in the order of 1.7 seconds.
Remove current from terminals B1-B2
Press pushbutton F1 and check that contact 00 on Board F has been open.
Check that LED 5 in the front of the relay has been turned off.
Repeat the process for phase B (terminals B3-B4) and for phase C (terminals B5-B6)
Under
Actual
⇓
Waveform Capture
menu retrieve the last oscillography recording stored, open it using GE_OSC program
and check that the two digital signals as well as the current signal were kept.
SELECT
NAME
SOURCE
Led 5
C Output Op 00
C Output_00_00
SELECT
NAME
SOURCE
Digital Channel 1
C Output Op_00_00
C Output Oper_00_00
Digital Channel 2
C Output_00_00
C Output_00_00
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...