GEK-113285A
G650 Generator Protection & Control System
5-77
5 SETTINGS
5.5 CONTROL ELEMENTS
5
5.5CONTROL ELEMENTS
The G650 incorporates the following control elements:
Setting Group
Underfrequency
Overfrequency
Synchrocheck (25)
Breaker Failure (50BF) (enhanced models only)
VT Fuse Failure (enhanced models only)
Pulse Counters
Analog Comparators
Frequency Rate of Change (81 df/dt)
Phase Shift or Loss of Mains (78V) (enhanced models only)
Loss of Excitation (40)
Accidental Energization (50/27)
Note
: for all control elements related to the breaker, it must be considered that all operations will be performed considering
the status of the switchgear configured as breaker. In
Setpoint > Relay Configuration > Switchgear
up to 16 switchgear
elements can be configured to operate and be monitored, but only one of them can be configured as a breaker, for
monitoring, number of openings and closings counters, (KI)
2
t.
5.5.1 SETTING GROUP
The settings used for setting table management are located in
Setpoint > Control Elements > Setting Group
:
Table 5–77: SETTING GROUP SETTINGS
The snapshot event setting enables or disables the snapshot event generation for this element.
For more detailed information go to section 5.4.1
SETPOINT > CONTROL ELEMENTS > SETTING GROUP
SETTING DESCRIPTION
NAME
DEFAULT
VALUE
STEP RANGE
Setting Grouping Permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Active Group
Active Group
GROUP 1
N/A
[GROUP 1 – GROUP 2 – GROUP 3]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Summary of Contents for Multilin G650
Page 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Page 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Page 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Page 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...